Psychrometric Calculator: Moist Air Properties
Enter dry-bulb temperature plus relative humidity, wet bulb, dew point or humidity ratio to get enthalpy, humidity ratio, specific volume and the rest. Altitude supported.
What is psychrometrics?
Psychrometrics deals with the properties of moist air, the mixture of dry air and water vapour. Air conditioning, ventilation, drying and dehumidification calculations all rest on these properties. The state of air is fixed by three things: pressure, dry-bulb temperature and one quantity that describes moisture. This calculator accepts moisture in four forms: relative humidity, wet-bulb temperature, dew point or humidity ratio.
Which relations are used?
First the saturation pressure of water p_ws is found (Hyland and Wexler correlation, ASHRAE Handbook of Fundamentals). Then in order:
- Vapour pressure: p_w = φ × p_ws
- Humidity ratio: W = 0.621945 × p_w / (p − p_w)
- Enthalpy: h = 1.006 × t + W × (2501 + 1.86 × t) kJ per kg of dry air
- Specific volume: v = 0.287042 × T × (1 + 1.607858 × W) / p
The dew point is the temperature whose saturation pressure equals p_w. Wet-bulb temperature is solved by iteration from the adiabatic saturation equation.
Example
At sea level, 25 °C and 50 percent relative humidity give a saturation pressure of 3169 Pa and a vapour pressure of 1585 Pa. The humidity ratio is 9.9 g/kg, enthalpy 50.3 kJ/kg, specific volume 0.858 m³/kg, dew point 13.9 °C and wet bulb 17.9 °C. The same air at 1000 m altitude holds 11.2 g/kg, because at lower pressure the same vapour pressure goes with less dry air.
Effect of altitude
A psychrometric chart is drawn for one pressure. At high altitude the humidity ratio and enthalpy errors from a sea level chart depend on temperature, humidity and pressure. A single percentage cannot describe every state. Enter the altitude to avoid that.
Limits
The calculation assumes ideal gas behaviour and omits the enhancement factor, which is the usual accuracy in air conditioning engineering. It is not meant for very high pressure, temperatures above 90 °C or precision measurement work.
Frequently asked questions
How do you calculate enthalpy from a psychrometric chart?
For example, at sea level pressure, air at dry bulb temperature 25 °C and 40 percent relative humidity has an enthalpy of 45.22 kJ/kg dry air, which is the state a chart would show. The moist air enthalpy equation adds dry air and water vapour contributions, excluding energy carried by liquid water and equipment efficiency.
Related calculators
-
HVAC and Thermodynamics
Dew Point and Relative Humidity Calculator
Find the dew point from temperature and relative humidity, or relative humidity from temperature and dew point. Absolute humidity and vapour pressure included. -
HVAC and Thermodynamics
Mixed Air Temperature and Enthalpy Calculator
Find the temperature, relative humidity, humidity ratio and enthalpy when two airstreams such as outdoor and return air mix. By mass and energy balance. -
HVAC and Thermodynamics
Dehumidification Capacity Calculator
From airflow and the temperature and humidity of entering and leaving air, find water removed (kg/h) and the total, sensible and latent cooling load. -
HVAC and Thermodynamics
Condensation and Mould Risk Calculator
Will a wall, window or pipe surface sweat at your room temperature and humidity? Enter the surface temperature or derive it from the U-value. -
HVAC and Thermodynamics
Air Conditioner Cooling Load and BTU Calculator (Rough Sizing)
Rough cooling load from room area, ceiling height, occupants, equipment and glazing gains in W, kW and BTU/h. For preliminary sizing only. -
HVAC and Thermodynamics
Boiler Size Calculator (Preliminary)
Heating power from building heat loss or from area and unit load, plus instantaneous hot water power from flow rate. Rough preliminary boiler sizing.
Found a mistake or something missing?
If a value looks wrong, a size is missing or you need a feature, write to us and we will fix it.