Dehumidification Capacity Calculator
From airflow and the temperature and humidity of entering and leaving air, find water removed (kg/h) and the total, sensible and latent cooling load.
How is dehumidification capacity calculated?
When air passes over a surface colder than its dew point, part of its water vapour condenses. Cooling coils in air handling units and portable dehumidifiers work this way. The moisture removed is the dry air mass flow times the difference between entering and leaving humidity ratios: ṁ_w = ṁ_a × (W_1 − W_2).
Dry air flow is the volumetric flow divided by the entering specific volume: ṁ_a = Q / v_1. Humidity ratios follow from temperature, relative humidity and air pressure through the psychrometric relations.
Cooling load
The total load the coil must remove is the enthalpy difference of the air less the energy carried away by the condensate: Q_t = ṁ_a × (h_1 − h_2) − ṁ_w × h_w. Part of it cools the air (sensible) and the rest condenses vapour (latent). The lower the sensible heat ratio, the larger the share of capacity spent on drying.
Example
Air at 18 000 cubic metres per hour enters a coil at 30 °C and 50 percent relative humidity and leaves saturated at 10 °C. The entering humidity ratio is 13.3 g/kg and the leaving one 7.66 g/kg. Dry air flow is 5.70 kg/s. About 116 kg of water condenses per hour and the cooling load is 197 kW, which is the result of the worked example in the ASHRAE Handbook of Fundamentals.
Things to watch
The tool warns when the leaving air is wetter than the entering air: air at 25 °C and 50 percent only gives up moisture once it is cooled below its dew point of 13.9 °C. The litres per day on an equipment label apply to one test condition, and capacity in your own room will differ.
Limits
The tool gives the load and the moisture removed for the leaving state you enter. Whether a particular coil reaches that state is decided by the manufacturer's selection software.
Related calculators
-
HVAC and Thermodynamics
Psychrometric Calculator: Moist Air Properties
Enter dry-bulb temperature plus relative humidity, wet bulb, dew point or humidity ratio to get enthalpy, humidity ratio, specific volume and the rest. Altitude supported. -
HVAC and Thermodynamics
Dew Point and Relative Humidity Calculator
Find the dew point from temperature and relative humidity, or relative humidity from temperature and dew point. Absolute humidity and vapour pressure included. -
HVAC and Thermodynamics
Air Conditioner Cooling Load and BTU Calculator (Rough Sizing)
Rough cooling load from room area, ceiling height, occupants, equipment and glazing gains in W, kW and BTU/h. For preliminary sizing only.
Found a mistake or something missing?
If a value looks wrong, a size is missing or you need a feature, write to us and we will fix it.