Boiler Size Calculator (Preliminary)
Heating power from building heat loss or from area and unit load, plus instantaneous hot water power from flow rate. Rough preliminary boiler sizing.
How is boiler capacity decided?
A boiler has two jobs: heating the building and producing domestic hot water. Capacity is chosen to suit both.
Heating power equals the heat the building loses on the coldest day. The right figure comes from a heat loss calculation. Without one, a rough value is area times a unit load: Q = A × q. An allowance for distribution loss and reheat is added on top.
Instantaneous hot water power is what it takes to bring flowing water up to temperature: Q_hw = ρ × c × V × Δt. In practical form, kW equals flow (L/min) times temperature rise divided by 14.33.
Why does hot water govern a combi?
Heating 10 litres per minute from 10 °C to 40 °C takes 10 × 30 / 14.33 = 20.9 kW. The heating load of a 120 m² flat is usually below that. Because a combi stops heating while hot water is drawn, the two are not added, the larger is taken. That is why combis of 24 kW and above are common in homes.
Example
A flat with a heat loss of 12 kW needs 13.8 kW of heating power with a 15 percent allowance. Ten litres per minute of hot water needs 20.9 kW. For a combi with hot water priority the required capacity is 20.9 kW, and the next standard size up is chosen.
About load per unit area
Heat load per square metre varies severalfold with climate, insulation, glazing ratio and the position of the flat (mid floor, top floor, corner). The tool therefore suggests no value. Use the figure from the room heating load tool or from a heat loss calculation.
Limits
This is a preliminary estimate. Storage systems, cascade boilers, commercial buildings and process heat need their own calculations. Final selection uses a heat loss calculation, a hot water demand calculation and manufacturer data.
Frequently asked questions
What size boiler do I need?
For 120 m² at an assumed 100 W/m² with a 15 percent allowance, heating needs 13.8 kW, while heating 10 L/min of water from 10 °C to 40 °C needs 20.93 kW, so a combi boiler with hot water priority needs 20.93 kW. This is a rough preliminary estimate with example inputs. Recalculate with the actual heat loss and tap flow, and select the appliance from manufacturer data.
How much floor area can a boiler heat?
A heating output of 23 kW covers 200 m² at an assumed load of 100 W/m² with a 15 percent allowance. This is not a universal floor area rating, since a lower unit load lets the same output heat a larger area. The figure covers space heating only, and instantaneous hot water often governs the rating of a combi boiler.
Related calculators
-
HVAC and Thermodynamics
Room Heating Load and Heat Loss Calculator (Preliminary)
Estimate a room's heat loss and required heating power from wall, window, roof and floor areas with their U-values and the indoor and outdoor temperatures. -
HVAC and Thermodynamics
Radiator Output Calculator (Preliminary)
Correct catalogue output to your own flow, return and room temperatures: what a radiator gives at low temperature and how much length or how many sections you need. -
HVAC and Thermodynamics
Air Conditioner Cooling Load and BTU Calculator (Rough Sizing)
Rough cooling load from room area, ceiling height, occupants, equipment and glazing gains in W, kW and BTU/h. For preliminary sizing only. -
HVAC and Thermodynamics
Chiller Capacity and Chilled Water Flow Calculator (Preliminary)
Chiller capacity (kW, TR) from cooling load, chilled water flow from capacity and temperature difference, capacity from flow. Condenser heat and compressor power too. -
HVAC and Thermodynamics
Condensation and Mould Risk Calculator
Will a wall, window or pipe surface sweat at your room temperature and humidity? Enter the surface temperature or derive it from the U-value. -
HVAC and Thermodynamics
COP, EER, SEER Converter and Comparison Calculator
Convert between COP, EER (BTU/Wh) and kW/ton. Efficiency from capacity and power input. Annual consumption and cost difference between two units from their SEER or SCOP.
Related tables
Found a mistake or something missing?
If a value looks wrong, a size is missing or you need a feature, write to us and we will fix it.