Wall U-Value Calculator (Thermal Transmittance)
U-value of a wall, roof or floor from up to six layers with EN ISO 6946 surface resistances. Also total resistance, heat flux and inside surface temperature.
What is a U-value?
The U-value (thermal transmittance) is the heat flow through 1 m² of a building element for a 1 K temperature difference between its two sides. Its unit is W/(m²·K). The lower the value, the harder it is for heat to pass and the better the insulation.
How is it calculated?
The thermal resistance of each layer is its thickness divided by its thermal conductivity: R = d / λ. The layer resistances are added, together with the resistances of the air films on both surfaces:
R_T = R_si + R₁ + R₂ + … + R_se and U = 1 / R_T
The internal and external surface resistances (R_si and R_se) are given in EN ISO 6946: R_si = 0.13 for walls, 0.10 for roofs, 0.17 for floors and R_se = 0.04 m²·K/W for the outside surface.
Example
Take a wall of 2 cm internal plaster (λ = 1.0), 19 cm brick (λ = 0.45), 5 cm insulation (λ = 0.035) and 8 mm external render (λ = 1.0). The resistances are 0.020, 0.422, 1.429 and 0.008 m²·K/W. With the surface resistances the total is 2.049 m²·K/W and the U-value is 1 / 2.049 = 0.49 W/(m²·K).
Notice that 5 cm of insulation provides 70 percent of the total resistance on its own while 19 cm of brick provides 21 percent. Without the insulation the U-value would be 1.61, so the wall would lose more than three times as much heat. The λ values here are only examples.
Where do I get thermal conductivity?
For insulation products the declared conductivity (λ_D) is on the label and in the declaration of performance. Design values for materials such as brick, concrete and plaster are tabulated in EN ISO 10456 and in national standards. This tool gives no material table from memory and asks you to enter the value.
Limits
The calculation is for a section of uniform layers without thermal bridges. Concrete columns and beams, fixings and metal profiles raise the real U-value. Whole building compliance and condensation checks (EN ISO 13788) are separate calculations.
Related calculators
-
HVAC and Thermodynamics
Insulation Thickness Calculator
Insulation thickness for a target U-value or an allowed heat loss: d = λ × (1 / U_target − R_existing). Rounds up to a commercial thickness and gives the resulting U-value. -
HVAC and Thermodynamics
Room Heating Load and Heat Loss Calculator (Preliminary)
Estimate a room's heat loss and required heating power from wall, window, roof and floor areas with their U-values and the indoor and outdoor temperatures. -
HVAC and Thermodynamics
Condensation and Mould Risk Calculator
Will a wall, window or pipe surface sweat at your room temperature and humidity? Enter the surface temperature or derive it from the U-value. -
HVAC and Thermodynamics
Heat Transfer Calculator: Conduction, Convection, Radiation
Conduction through a plane wall (up to three layers) and a pipe wall, plus convection and radiation from a surface. Fourier, Newton and Stefan-Boltzmann laws with worked steps.
Found a mistake or something missing?
If a value looks wrong, a size is missing or you need a feature, write to us and we will fix it.