Motor Starting Current Calculator
Approximate starting current of an induction motor for direct on line, star delta, autotransformer and current limited starting. The starting ratio comes from the datasheet.
What is motor starting current?
When an induction motor is switched on at standstill it draws several times its rated current until it speeds up. This is the starting, inrush or locked rotor current. Motor datasheets give it as a ratio to rated current (I_a / I_n).
Calculation
First find the rated current. For a three phase motor:
I_n = P / (√3 × V × η × cos φ)
P is shaft power, η efficiency and cos φ the power factor. Then, depending on the starting method:
- Direct on line: I_a = k × I_n
- Star delta: I_a = k × I_n / 3
- Autotransformer: I_a = a² × k × I_n (a is the tap ratio)
- Soft starter or drive: the current limit that is set
Example
A 15 kW, 400 V motor with 90 percent efficiency and a power factor of 0.85 has a rated current of 15000 / (1.732 × 400 × 0.9 × 0.85) = 28.3 A. With a datasheet starting ratio of 6 it draws 170 A direct on line and 56.6 A with star delta. Direct on line, the apparent power is 117.6 kVA.
Lower current means lower torque
With star delta the starting torque also falls to one third. With an autotransformer torque falls with the square of the tap ratio. On machines that are heavy to start, a reduced current method may not get the motor moving.
Limits
The starting ratio is specific to the motor and must come from its datasheet. The tool estimates the steady current only. The first instant peak, the run up time and the voltage dip are not calculated. This result alone is not enough to select protection, cables or a generator.
Related calculators
-
Electrical and Electronics
kW, kVA, HP and Amps Converter
Convert kW to kVA with power factor, kW to horsepower (metric and mechanical), and kW or kVA to amps. Single and three phase, with efficiency. -
Electrical and Electronics
Electrical Power, Current and Voltage Calculator (Single and Three Phase)
Find power, current, voltage or power factor for single and three phase AC. Active, apparent and reactive power together. -
Electrical and Electronics
Generator Sizing Calculator (kVA)
Generator rating (kVA, kW) and current from connected load, demand factor and spare margin. Momentary kVA when the largest motor starts. All factors are user inputs. -
Electrical and Electronics
Cable Size and Voltage Drop Calculator
Voltage drop, line resistance and power loss for copper and aluminium cables. Single phase, three phase and DC. Smallest standard size for a voltage drop limit.
Found a mistake or something missing?
If a value looks wrong, a size is missing or you need a feature, write to us and we will fix it.