Heat Pump Electricity Consumption and Boiler Comparison
Electrical input from heating output and COP, annual consumption and cost from heat demand and SCOP. Annual running cost against a gas boiler, with the break even SCOP.
How much electricity does a heat pump use?
A heat pump does not make heat, it moves it: a compressor driven by electricity carries heat from outdoor air, the ground or water into the building. The ratio of heat delivered to electricity drawn is the COP:
P = Q / COP
A unit with a COP of 4 delivering 10 kW of heat draws 2.5 kW of electricity. The other 7.5 kW comes from the environment. For a resistance heater the ratio is 1, so the same heat takes four times the electricity.
Annual consumption
COP changes with outdoor temperature, so annual figures use the seasonal average, SCOP: E = Q_annual / SCOP. A house needing 12 000 kWh of heat a year uses 3000 kWh of electricity with a heat pump whose SCOP is 4.
If you do not know your annual heat demand, take it from your gas bills: annual gas use (kWh) times boiler efficiency.
Comparison with a boiler
For the same heat a boiler burns Q_annual / (η × H) of fuel, where η is the boiler efficiency and H the heating value per unit of fuel.
Example: for 12 000 kWh of heat a 90 percent efficient boiler burns 1253 m³ of gas at 10.64 kWh/m³. Which system is cheaper to run is shown by the break even SCOP: SCOP_b = f_electricity × η × H / f_fuel. If the real seasonal efficiency of your heat pump is above it, heating costs less.
What affects the result?
The biggest factor is flow temperature. Low temperature systems such as underfloor heating give high efficiency and old high temperature radiators give low efficiency. Efficiency falls as outdoor air gets colder, and air source units run defrost cycles. Read the SCOP on the label for your own climate zone and water temperature.
Limits
The tool compares running cost only. Purchase and installation, maintenance, standing charges and subsidies are not included. To see when the investment pays for itself use the energy payback calculator.
Frequently asked questions
How much electricity does a heat pump use at COP 3.5?
A heat pump delivering 10 kW of heat draws 2.857 kW of electricity at a COP of 3.5. This describes one operating point, with COP supplied by the user. Outdoor and water temperatures change efficiency, while auxiliary heaters and pumps may add to the electrical demand.
How much electricity does a 16 kW heat pump draw?
A useful heating output of 16 kW requires 4 kW of electrical input at an assumed COP of 4. Rated heating capacity is not the same as electricity consumption. This result assumes one operating point, while annual use requires seasonal efficiency and the building annual heat demand.
Related calculators
-
HVAC and Thermodynamics
COP, EER, SEER Converter and Comparison Calculator
Convert between COP, EER (BTU/Wh) and kW/ton. Efficiency from capacity and power input. Annual consumption and cost difference between two units from their SEER or SCOP. -
HVAC and Thermodynamics
Energy Cost and Payback Period Calculator
Simple and discounted payback, net present value and internal rate of return for insulation, heat pump or solar investments. With price escalation and annual kWh and CO₂ savings. -
HVAC and Thermodynamics
Room Heating Load and Heat Loss Calculator (Preliminary)
Estimate a room's heat loss and required heating power from wall, window, roof and floor areas with their U-values and the indoor and outdoor temperatures. -
HVAC and Thermodynamics
Boiler Size Calculator (Preliminary)
Heating power from building heat loss or from area and unit load, plus instantaneous hot water power from flow rate. Rough preliminary boiler sizing. -
HVAC and Thermodynamics
Heating and Cooling Degree Days Calculator (HDD, CDD)
Heating (HDD) and cooling (CDD) degree days from monthly mean or daily temperatures, with adjustable base and threshold. Annual heat demand and fuel use from degree days. -
HVAC and Thermodynamics
Radiator Output Calculator (Preliminary)
Correct catalogue output to your own flow, return and room temperatures: what a radiator gives at low temperature and how much length or how many sections you need.
Found a mistake or something missing?
If a value looks wrong, a size is missing or you need a feature, write to us and we will fix it.