COP, EER, SEER Converter and Comparison Calculator
Convert between COP, EER (BTU/Wh) and kW/ton. Efficiency from capacity and power input. Annual consumption and cost difference between two units from their SEER or SCOP.
What do COP, EER and SEER tell you?
An air conditioner or heat pump moves more heat than the electricity it draws. Its efficiency is the ratio of the cooling or heating it delivers to the electrical power it takes.
- COP (coefficient of performance): capacity (W) over power input (W). It has no unit. A unit with a COP of 3.5 moves 3.5 kW of heat with 1 kW of electricity.
- EER (energy efficiency ratio): the same ratio in cooling. On European labels it is in W/W and equals the COP. US sources give it in BTU/Wh.
- SEER and SCOP: seasonal averages. Total energy delivered over a season divided by total electricity used, part load operation included.
Conversion relations
Since 1 watt is 3.412 BTU/h, EER (BTU/Wh) = 3.412 × COP. For chillers, kW/ton = 3.517 / COP = 12 / EER. Example: a COP of 3.5 gives an EER of 11.94 BTU/Wh and 1.005 kW/ton.
Comparing two units
Annual electricity use is the annual cooling demand divided by SEER. Of two air conditioners delivering 3000 kWh of cooling a year, the one with SEER 5.1 uses 588 kWh and the one with SEER 8.5 uses 353 kWh. The 235 kWh difference times your price per kWh is the annual saving.
If you do not know the annual cooling demand, a rough figure is capacity times equivalent full load hours per year. That number of hours varies widely with climate and use.
Points to watch
Label values are measured under standard test conditions. European and US SEER use different temperature profiles, so a unit conversion does not equate them: compare values rated to the same standard. Real consumption departs from the label with outdoor temperature, set point, installation quality and filter cleanliness.
Frequently asked questions
How do you calculate COP from EER?
Dividing an example EER of 12 BTU/Wh by the conversion factor 3.412142 at the same operating point gives a COP of 3.517, expressing thermal output divided by electrical input. This conversion does not calculate seasonal performance or make ratings based on different test conditions and seasonal evaluation methods directly equivalent.
Related calculators
-
HVAC and Thermodynamics
Heat Pump Electricity Consumption and Boiler Comparison
Electrical input from heating output and COP, annual consumption and cost from heat demand and SCOP. Annual running cost against a gas boiler, with the break even SCOP. -
HVAC and Thermodynamics
Air Conditioner Cooling Load and BTU Calculator (Rough Sizing)
Rough cooling load from room area, ceiling height, occupants, equipment and glazing gains in W, kW and BTU/h. For preliminary sizing only. -
HVAC and Thermodynamics
Chiller Capacity and Chilled Water Flow Calculator (Preliminary)
Chiller capacity (kW, TR) from cooling load, chilled water flow from capacity and temperature difference, capacity from flow. Condenser heat and compressor power too. -
HVAC and Thermodynamics
Energy Cost and Payback Period Calculator
Simple and discounted payback, net present value and internal rate of return for insulation, heat pump or solar investments. With price escalation and annual kWh and CO₂ savings. -
Electrical and Electronics
Electrical Power, Current and Voltage Calculator (Single and Three Phase)
Find power, current, voltage or power factor for single and three phase AC. Active, apparent and reactive power together. -
HVAC and Thermodynamics
Boiler Size Calculator (Preliminary)
Heating power from building heat loss or from area and unit load, plus instantaneous hot water power from flow rate. Rough preliminary boiler sizing.
Found a mistake or something missing?
If a value looks wrong, a size is missing or you need a feature, write to us and we will fix it.