UPS Sizing and Runtime Calculator
UPS rating (VA) from the load total, approximate runtime from a battery bank and the battery capacity for a wanted runtime. All factors are user inputs.
How is a UPS sized?
A UPS has two limits: apparent power (VA) and active power (W). Their ratio is the UPS output power factor. The load must stay below both.
- Apparent power of the load: S = P / load power factor
- VA equivalent of the watt limit: P / UPS power factor
- Required UPS rating: the larger of the two × (1 + spare margin)
Example
A load drawing 3000 W at a power factor of 0.8 is 3750 VA. For a UPS with an output power factor of 0.9 the watt limit asks for 3333 VA, so 3750 VA governs. With a 25 percent margin at least 4687.5 VA is needed: choose the next standard rating up.
Runtime
t = n × V × Ah × k × η / P
n is the number of batteries, V and Ah the voltage and capacity of one battery, η the inverter efficiency and k the usable share of capacity. Two 12 V 9 Ah batteries hold 216 Wh. With k = 0.6 and η = 0.9 the load receives 116.6 Wh, so a 600 W load runs for about 11.7 minutes.
Why the usable share matters
The Ah figure on a battery applies to a long discharge (often 10 or 20 hours). A UPS drains its batteries in minutes, and at that rate a battery delivers only part of its rated capacity. The share depends on battery type, discharge time and cut off voltage: the right value is in the battery manufacturer's constant power discharge table. The tool does not suggest one.
What this tool does not cover
Inrush currents, harmonic loads, temperature, battery ageing and the UPS overload curve are not included. The result is a first estimate: for critical loads the selection must be made by a qualified engineer using the UPS and battery manufacturers' data.
Related calculators
-
Electrical and Electronics
Battery Capacity Calculator (Ah, Wh and Runtime)
Convert amp hours to watt hours, find how long a battery runs a load and the Ah needed for a wanted runtime. With efficiency and usable capacity. -
Electrical and Electronics
Battery Series and Parallel Connection Calculator
Total voltage, capacity (Ah) and energy (Wh) of cells or batteries in series and parallel. Series and parallel counts needed for a target voltage and capacity. -
Electrical and Electronics
Inverter Size Calculator
Inverter rating from the load total, surge power when a motor load starts and the current drawn from the battery. Demand, margin and surge factors are user inputs. -
Electrical and Electronics
kW, kVA, HP and Amps Converter
Convert kW to kVA with power factor, kW to horsepower (metric and mechanical), and kW or kVA to amps. Single and three phase, with efficiency.
Found a mistake or something missing?
If a value looks wrong, a size is missing or you need a feature, write to us and we will fix it.