Inverter Size Calculator
Inverter rating from the load total, surge power when a motor load starts and the current drawn from the battery. Demand, margin and surge factors are user inputs.
How is an inverter sized?
A battery inverter has two ratings: the power it can deliver continuously and the surge power it can hold for a short time. Both must be checked.
Continuous rating
Add the power of the devices on the inverter, apply a demand factor for those that do not run together and add a spare margin:
P_inv = P × k_e × (1 + y)
Surge power
Motor driven devices such as fridges, pumps and compressors draw several times their rated power when they start. The worst moment is when such a device switches on while the other loads are running:
P_peak = running load − P_k + k_k × P_k
The surge rating in the inverter datasheet must exceed this and last for the whole start.
Example
Out of a 1500 W total, 500 W is a fridge with a starting multiple of 3. With a 25 percent margin the continuous rating is 1500 × 1.25 = 1875 W. At start 1500 − 500 + 3 × 500 = 2500 W is needed. On a 24 V battery at 90 percent efficiency the running load draws 1500 / (0.9 × 24) = 69 A.
Current on the battery side
At low voltage the same power means very high current. In a 12 V system 1000 W takes 83 A without losses, or about 93 A at 90 percent efficiency. That current sets the cable size, the fuse and the battery capacity, all of which need their own calculation.
Limits
The starting multiple varies a lot from device to device and the tool does not suggest a value. The result is a first estimate: confirm it with the manufacturer datasheet and the applicable standard.
Frequently asked questions
What size inverter do I need?
With all 1500 W running together and an example margin of 25 percent, the minimum continuous rating is 1875 W, and peak demand reaches 2500 W while the included 500 W load starts at 3 times its rating. This is a preliminary estimate. Verify the starting multiple, surge duration, battery, wiring, protection and apparent power limits against the equipment data.
Related calculators
-
Electrical and Electronics
Battery Capacity Calculator (Ah, Wh and Runtime)
Convert amp hours to watt hours, find how long a battery runs a load and the Ah needed for a wanted runtime. With efficiency and usable capacity. -
Electrical and Electronics
Battery Series and Parallel Connection Calculator
Total voltage, capacity (Ah) and energy (Wh) of cells or batteries in series and parallel. Series and parallel counts needed for a target voltage and capacity. -
Electrical and Electronics
UPS Sizing and Runtime Calculator
UPS rating (VA) from the load total, approximate runtime from a battery bank and the battery capacity for a wanted runtime. All factors are user inputs. -
Electrical and Electronics
Solar Panel Output Calculator (PV System Yield)
Installed power (kWp) and daily, monthly and annual yield from panel count and rating. Panels needed for a given consumption. Peak sun hours and efficiency are user inputs. -
Electrical and Electronics
Cable Size and Voltage Drop Calculator
Voltage drop, line resistance and power loss for copper and aluminium cables. Single phase, three phase and DC. Smallest standard size for a voltage drop limit. -
Electrical and Electronics
AC Impedance and Phase Angle Calculator (Series and Parallel RLC)
XL, XC, impedance, phase angle and power factor of a series or parallel R, L, C circuit. With a voltage: current, active, reactive and apparent power. With steps.
Found a mistake or something missing?
If a value looks wrong, a size is missing or you need a feature, write to us and we will fix it.